Synergrid C10/26 list: is my inverter on the list – and what if it is not?

What the Synergrid C10/26 list is, why grid operators and inspection bodies require it, how to read reference, firmware, Smax and restrictions correctly – and how to check a device in seconds.

Published on 26 August 2026 7 min

Synergrid C10/26 list: is my inverter on the list – and what if it is not?

Short answer: the Synergrid C10/26 list is the Belgian register of every inverter, hybrid inverter and battery system homologated under the technical prescription C10/11 (Annex D). As a rule, the grid operators (Fluvius, ORES, RESA, Sibelga) accept only listed devices at registration – in the listed firmware version. If a device is not listed, the only route left is an individual proof of conformity against C10/11, which the grid operator has to accept. To find out whether a device is on it, use the free Synergrid C10/26 check by PlanElec – the data is reconciled with the official list every day.

What is the Synergrid C10/26 list?

Synergrid is the federation of Belgian electricity and gas grid operators. The prescription C10/11 defines the technical requirements that decentralised generation units (PV inverters, home batteries, CHP, wind) must meet on the low-voltage grid: protection functions during grid disturbances, frequency and voltage behaviour, power control.

The C10/26 list is its practical result: manufacturers have their devices tested against C10/11; approved device types are published with reference number, firmware version and technical data. Synergrid keeps the list up to date as an Excel file; the current edition refers to C10/11 edition 2.4 (15/10/2025) and contains more than 8,000 active devices from around 290 brands.

Why the list matters for registration and inspection

StepRole of the C10/26 list
Registration with the grid operatorFluvius, ORES, RESA and Sibelga require a listed device; the inverter type is requested in the registration form
Conformity inspectionThe inspection body checks the inverter against the single-line diagram and the manufacturer data
Injection approvalWithout a homologated device the grid operator does not release feed-in
Firmware update or replacementA new firmware version or a replacement device must be listed again

For residential PV systems up to 10 kVA, AREI Art. 7.112 (requirements on the electrical installation itself) applies in addition – both must be right. The guide PV system in the single-line diagram shows what the diagram looks like.

How to read a list entry

Each row describes one combination of model and firmware. The key columns:

ColumnMeaning
Reference (e.g. GLV052-09-0003)Synergrid homologation number of the device – complements brand and model in the registration (not always unique per model)
Brand / series / modelManufacturer designation, exactly as on the rating plate
FirmwareTested software version; the homologation applies to this version only
Pac,r (W)Rated active power at the AC output
Smax (VA)Maximum apparent power – decisive for the power class; grid operators typically cap single-phase generation units at around 5 kVA (check the exact threshold with your grid operator)
PhasesSingle-phase or three-phase
ApplicationSolar, storage, CHP, wind, backup
RestrictionsConditions under which the device is admitted (see below)
Homologated sinceDate of final (or provisional) homologation

Why the firmware version counts

The protection functions under C10/11 are software. A device running a firmware other than the listed one counts as not homologated at registration and inspection – even if the model itself is on the list. Check the firmware on the device or in the manufacturer's app and compare it with the list entry.

Interpreting restrictions correctly

Restriction on the listWhat it means
Only within a module < 800 WAdmitted solely as part of a plug-in generation unit (balcony solar, plug-in battery)
Small generating installations onlyNot for larger installations with extended requirements
High-voltage connection onlyNot for domestic connections on the low-voltage grid
Backup power system onlyHomologated for backup supply only, not for feeding into the grid – the unit supplies an isolated part of the installation during an outage

Plug-in solar and plug-in batteries: the same list

Micro-inverters and plug-in batteries up to 800 W – Marstek, Zendure, Anker Solix, HomeWizard or Hoymiles, for instance – must also be on the C10/26 list, usually with the restriction "only in module < 800 W". A device sold in Germany or the Netherlands is not automatically admitted in Belgium: the Belgian grid protection settings (C10/11) differ, and the manufacturer must have the Belgian variant homologated separately. So check before buying whether the specific model is listed. Even a listed plug-in device must be registered with the grid operator; the electrical installation itself remains subject to the AREI. If you are specifically after a battery, use the Synergrid C10/26 check for home batteries – the same list, but written for batteries and hybrid inverters.

Common mistakes in practice

  1. Model checked without its suffixSUN2000-8KTL-M0 and SUN2000-8KTL-M1 are different entries.
  2. Firmware not compared – the device is listed but installed with an older version.
  3. Expired homologation overlooked – Synergrid withdraws entries; the device then appears under "expired".
  4. Imported from abroad – same name, different country variant without Belgian homologation.
  5. Battery forgotten – the battery inverter needs a list entry too, not only the PV inverter. See Home battery and AREI.

Check a device in seconds

The Synergrid C10/26 check loads the official list daily and makes it searchable:

  1. Type the brand – suggestions show how many models are listed per brand.
  2. Refine the model – keep typing until the exact model appears; expired entries are flagged.
  3. Read the result – the table shows firmware, Smax, Pac, phases, application, restrictions and the Synergrid reference; sortable and filterable by phases, segment and status.
  4. No match? – the tool suggests technically comparable homologated devices of the same power class.

Filters and sorting are kept in the URL, so the link can be passed straight to a customer or colleague.

Limits of the tool

The tool is a search aid, not an official statement. The official list on synergrid.be remains authoritative; in case of discrepancy the official list prevails. The tool does not check the electrical installation itself (protection, RCD, cable size, isolator) – that is what the AREI self-check in PlanElec's single-line diagram is for.

Frequently asked questions

Do I have to put the Synergrid reference in the registration? Grid operators primarily ask for brand, model and firmware version. The GLV reference is a useful addition but not always unique per model: Synergrid sometimes assigns the same reference to several models. So state the reference and the model designation.

My device is listed, but the entry is "expired" – what now? The homologation has been withdrawn or has lapsed. For new installations the device is no longer admitted; existing installations are generally unaffected. When in doubt, ask the grid operator.

Does the list also apply in Wallonia and Brussels? Yes. C10/11 and C10/26 are Synergrid prescriptions and apply nationwide to all distribution grid operators.

How often does the list change? Synergrid publishes new editions regularly; the tool picks up changes daily and shows the date of its data.